Conduit Fill Calculator

Calculate conduit fill percentage for multiple cable groups and the required internal diameter for your chosen limit.

Conduit Fill Calculator

FREE ONLINE TOOL
Formula and assumptions

Fill (%) = 100 × Σ(n × d²) / D²; required D = √(Σ(n × d²) / (limit / 100)).

Uses cable outside diameter including insulation and conduit internal diameter. Fill limit is user supplied, not a code default. Area calculation does not verify pulling, bends, heat or local compliance.

3 cables of 8 mm OD in a 25 mm ID conduit: 30.72% fill; at a user limit of 40%, required ID = 21.91 mm.

STEP BY STEP

How to use conduit fill calculator

  1. Check the input units and assumptions.
  2. Review the result and example.

IN PRACTICE

Example

3 cables of 8 mm OD in a 25 mm ID conduit: 30.72% fill; at a user limit of 40%, required ID = 21.91 mm.

GOOD TO KNOW

Which formula and assumptions are used?

Fill (%) = 100 × Σ(n × d²) / D²; required D = √(Σ(n × d²) / (limit / 100)). Uses cable outside diameter including insulation and conduit internal diameter. Fill limit is user supplied, not a code default. Area calculation does not verify pulling, bends, heat or local compliance.