Fan Laws: How Speed Changes Airflow, Pressure and Power

All tools: Engineering Tools

Use fan affinity laws to compare airflow, pressure and power at different rotational speeds under similar conditions.

Open the free tool →

Formula and units

For the same fan and similar air density: Q₂/Q₁ = N₂/N₁; pressure₂/pressure₁ = (N₂/N₁)²; power₂/power₁ = (N₂/N₁)³. Q is volume flow, N is rotational speed, pressure is fan pressure and power is shaft power.

Worked example

Increasing speed by 10% gives a theoretical airflow factor of 1.10, pressure factor 1.21 and power factor 1.331. A small speed increase can therefore require a much larger power increase.

Assumptions and limits

Affinity laws are estimates for comparable operation. System resistance, fan efficiency, density, inlet conditions, stall and motor limits affect actual results. Do not exceed the fan or motor operating envelope; verify the duty point on manufacturer curves.